EP-SC&EPS-SC SERIES THREE-PHASE SOUNDPROOF DIESEL GENERATOR SETS
MAIN SPECIFICATIONS OF GENERATOR SETS POWERED BY LION ENGINE(50Hz) | ||||||||||||||
GENSET MODEL | Open type model | GF-SC48 | GF-SC58 | GF-SC68 | GF-SC80 | GF-SC91 | GF-SC112 | GF-SC128 | GF-SC150 | GF-SC200 | GF-SC225 | GF-SC250 | GF-SC300 | GF-SC400 |
Soundpoof model | GFS-SC48 | GFS-SC58 | GFS-SC68 | GFS-SC80 | GFS-SC91 | GFS-SC112 | GFS-SC128 | GFS-SC150 | GFS-SC200 | GFS-SC225 | GFS-SC250 | GFS-SC300 | GFS-SC400 | |
Contionous output(KW/KVA) | 48/60 | 58/72.5 | 68/85 | 80/100 | 91/144 | 112/140 | 128/160 | 150/187.5 | 200/250 | 225/281 | 250/312.5 | 300/375 | 400/500 | |
Standby output(KW/KVA) | 52.8/66 | 63.8/80 | 75/93.5 | 88/110 | 100/125 | 123/154 | 140.8/176 | 165/206 | 220/275 | 247.5/309 | 275/345 | 330/412 | 440/550 |
Rating Definitions
Continuous Power
These ratings are applicable for supplying continuous electrical power(at variable load)in lieu of commercially purchased power.There is no the annual hours of operation and this model can supply 10% overload power for 1 hore in 12 hours
Standby power
These ratings are applicable for supplying continuous electrical power(at variable load)in the event of a utility power failure.No overload is permitted on these ratings.The alternator on this model is peak continuous rated (as defined in ISO8528-3)at 27℃.
TECHNICAL DATE(50Hz) | |||||||||||||
DISEL ENGINE MODEL | 4135D-1 | 4135AD | 4135AZD-1 | 4135AZD | 4135AZD-2 | 6135JZD | 6135AZD-1 | G128ZLD | G128ZLD1 | G128ZLD11 | 12V135AZD | 12V135BZLD | 12V135BZLD1 |
Continuous output KW | 58.8 | 73.5 | 90 | 108 | 117 | 140 | 155 | 187 | 236 | 280 | 300 | 405 | 505 |
Standby output KW | 65 | 81 | 99 | 119 | 129 | 154 | 171 | 206 | 260 | 308 | 330 | 445 | 555 |
Rate speed(r/min) | 1500 | ||||||||||||
Bore(mm)*Stroke(mm) | 135*140 | 135*150 | 135*140 | 135*150 | 135*155 | ||||||||
Compression ratio | 16.5:1 | 17:1 | 16:1 | 17:1 | 16:1 | 16.4:1 | 16.4:1 | ||||||
Fuel Consumption(g/kw.h) | ≤225 | ≤220 | ≤225 | ≤220 | ≤210 | ≤220 | |||||||
Aspiration | Naturally | Turbocharged | Turbo&Intercooler | ||||||||||
Discharge(L) | 8 | 8.6 | 12 | 12.88 | 26 | 26.6 | 26.6 | ||||||
Noise dB(A)1m | ≤117 | ≤119 | |||||||||||
Effluent standard | Meet the regulation JB8891 | TIERI | Meet the regulation JB8891 | ||||||||||
Lube capacity (L) | 25 | 28 | 75 | ||||||||||
Water coolant capacity(L) | 16 | 24 | 23 | 48 | |||||||||
exhaust(FSN) | ≤3 | ≤2.0 | ≤3 | ≤3.1 | ≤2.0 | ≤2.5 | |||||||
exhaust temperature(℃) | ≤550 | ≤600 | ≤500 | ||||||||||
Speed Governor | Mechanical | Electric | |||||||||||
Stability govern rate(%) | 5 | ||||||||||||
Waveform Distortion(%) | ≤0.5 | ||||||||||||
Stabilization of speed(S) | ≤5 | ||||||||||||
Min no-load speed(r/min) | ≤600 | ≤700 | ≤600 | ≤750 | ≤750 | ||||||||
Lube Consumption(g/kw.h) | ≤2 | ≤1 | ≤0.7 | ||||||||||
Starting method | Electrical Start(24V) | ||||||||||||
ALTERNATOR MODEL | YK224E | YK224F | YK224G | YK274C | YK274D | YK274E | YK274F | YK274H | YK314C | YK315D | YK316E | YK317F | YK354D |
Continuous output (KW/KVA) | 48/60 | 58/72.5 | 68/85 | 80/100 | 91/114 | 112/140 | 128/160 | 160/200 | 200/250 | 236/295 | 260/325 | 304/380 | 400/500 |
Power efficiency | 88.8% | 89.9% | 90.2% | 90.3% | 90.7% | 91.7% | 92.4% | 92.3% | 92.9% | 93.9% | 93.5% | 93.4% | 94.3% |
Voltage regulation | ±1% engine governing | ||||||||||||
Waveform distortion | No load≤1.5% and non-distorting blanced linear load ≤5% | ||||||||||||
THF/TIF | <2% /<50 |